코어재에 따른 철제 방화문의 내화성능에 관한 연구 |
서희원, 안재홍, 최동호 |
|
A Study on the Fire Resistance Performance of the Steel Fire Doors Depending on Core Material |
Hee Won Seo, Jae Hong An, Dong Ho Choi |
|
|
|
Abstract |
Fire doors are installed on the openings in buildings to protect fire spreading in the event of fire. In foreign countries, fire doors whose fire resistance performance is from 20 minutes to 180 minutes are installed depending on required fire resistance performance of where fire doors are installed. But, in Korea, it is difficult to protect fire spreading in the event of fire because fire doors only having integrity of 1 hour are installed regardless of the position of fire doors. Therefore, it is needed to improve the system related to fire doors by strengthening the required fire resistance performance depending on where fire doors are installed and introducing insulation performance. To do so, the performance verification of the existing fire doors must be done first. In this study, fire resistance performance of the steel fire doors which are used widely depending on core material was evaluated. As a result, most specimens had the integrity performance and secured insulation performance of around 10 minutes depending on core material. |
Key Words:
Fire door; Fire resistance performance; Core material; Insulation performance |
요지 |
화재시 건물내의 화재확산방지를 위해서 개구부에는 방화문이 설치된다. 외국에서는 방화문이 설치되는 부위의 내화성능 등을 고려하여 20분~180분의 방화문을 구분하여 적용하고 있으나, 국내에서는 일률적으로 1시간의 차염 성능만을 적용토록 하고 있어 화재시 충분한 화재확산방지를 기대하기 어렵다. 이에 국내에서도 방화문이 적용되는 위치에 따라 요구되는 내화성능을 강화하고, 차열성능을 확보토록 제도를 개선하여야 할 필요성이 있으며, 이를 위해서는 기존 방화문의 성능 검증이 선행되어야 한다. 이에 본 연구에서는 제도 개선을 위한 기초자료로 활용하기 위하여 방화문으로 널리 사용되는 철제 방화문의 코어재 종류에 따른 내화성능을 평가하였으며 대부분의 시험체가 차염 성능을 확보하고, 코어재에 따라 10분 안팎의 차열 성능을 확보하고 있음을 확인하였다. |
핵심용어:
방화문; 내화성능; 코어재; 차열성능 |
|