| 소규모 리튬이온배터리 화재적응 소화약제 및 장치의 성능평가절차 고찰과 제안 |
|
강현1, 최한빛2, 권오상3 |
1정회원, 한국건설기술연구원 화재안전연구본부 수석연구원⋅공학박사 2정회원, 한국건설기술연구원 화재안전연구본부 박사 후 연구원⋅공학박사 3정회원, 한국건설기술연구원 화재안전연구본부 연구위원⋅공학박사 |
| Performance Evaluation Procedures for Fire Extinguishing Agents and Devices in Small-Scale Lithium-Ion Battery Fires |
|
Hyun Kang1, Han-Bit Choi2, Oh Sang Kweon3 |
1Member, Ph.D., Senior Researcher, Fire Research Institute, KICT 2Member, Ph.D., Post-Doctoral Researcher, Fire Research Institute, KICT 3Member, Ph.D., Research Fellow, Fire Research Institute, KICT |
Corresponding author:
Oh Sang Kweon, Tel: +82-31-369-0546, Fax: +82-31-369-0540, Email: oskweon@kict.re.kr |
|
Received: 26 August 2026 • Revised: 27 August 2026 • Accepted: 31 August 2026 |
|
|
| Abstract |
|
Small-scale lithium-ion battery fires involve thermal runaway, propagation to adjacent cells, and possible re-ignition; therefore, flame suppression alone does not adequately reflect the extinguishing performance. This study reviewed the major test elements of KFI 630 and NTA 8133 and proposed an improved procedure based on fire and extinguishing tests using small-scale pouch-type lithium-ion batteries. In the free-burn tests, thermal runaway propagated through the five-cell test specimen within approximately 60-120 s, whereas the suppression tests showed different cell temperature histories and subsequent thermal runaway propagation behaviors depending on the extinguishing agent. The proposed revision maintains the KFI test configuration, heating method, and one-hour reignition observation period, while additionally recording the cell-by-cell thermal runaway timing, flame extinguishment time, and actual agent consumption. Additionally, a supplementary procedure is also proposed to evaluate the thermal stabilization and thermal runaway propagation delay using cell-temperature histories, cooling performance, propagation time, and the total number of cells undergoing thermal runaway. Further replication is required to establish the reproducibility and quantitative acceptance criteria for these proposed indicators. |
| Key Words:
Small-scale Lithium-ion Battery, Thermal Runaway, Fire Extinguishing Performance, Cooling Performance, Thermal Runaway Propagation |
| 요지 |
|
소규모 리튬이온배터리 화재는 열폭주, 인접 셀로의 열전이 및 재발화 특성으로 인해 화염소거만으로 소화성능을 충분히 평가하기 어렵다. 본 연구에서는 현행 KFI 630과 NTA 8133의 주요 소화시험 요소를 검토하고 소규모 파우치형 리튬이온배터리의 화재 및 소화시험 결과를 바탕으로 시험절차의 개선방향을 제안하였다. 무소화시험에서 5개 셀의 전체 열폭주 전이는 약 60~120 s 범위에서 나타났으며, 소화약제 적용시험에서는 약제 종류에 따라 셀별 온도거동과 후속 열폭주 전이특성에 차이가 확인되었다. 이에 현행 KFI의 시험체, 가열방식 및 1 h 재발화 관찰체계를 유지하면서 셀별 열폭주 발생시각, 화염소거시간 및 실제 소화약제 사용량을 정량적으로 기록하는 보완안을 제시하였다. 또한 기존 합격판정과 별도로 셀별 온도변화, 냉각성능, 열폭주 전이시간 및 열폭주 발생 셀 수를 이용하여 소화약제의 열적 안정화 및 열폭주 전이 지연효과를 평가하는 절차를 제안하였다. 다만 제안한 정량지표의 성능기준 설정을 위해서는 향후 반복시험을 통한 재현성 검증이 필요하다. |
| 핵심용어:
소규모 리튬이온배터리, 열폭주, 소화성능, 냉각성능, 열폭주 전이 |
|