| 방화셔터 복사열에 의한 수용물품 착화실험을 통한 복사열 차단 성능기준 제안 |
|
서희원1, 손종원2, 심현보3, 김대회4, 홍성호5 |
1정회원, 한국화재보험협회부설방재시험연구원 방재연구센터 수석연구원 2한국화재보험협회부설방재시험연구원 방재연구센터 선임연구원 3한국화재보험협회부설방재시험연구원 방재연구센터 전문위원 4정회원, 한국화재보험협회부설방재시험연구원 방재연구센터 수석연구원 5한국화재보험협회부설방재시험연구원 방재연구센터 수석연구원 |
| A Proposal for Radiant Heat-Blocking Performance Criteria based on Ignition Experiments of Commodities Caused by Fire Shutter Radiant Heat |
|
Heewon Seo1, Jongwon Shon2, Hyeonbo Shim3, Daehoi Kim4, Sungho Hong5 |
1Member, Principal Researcher, Risk & Safety Research Center, Fire Insurers Laboratories of Korea 2Senior Researcher, Risk & Safety Research Center, Fire Insurers Laboratories of Korea 3Research Fellow, Risk & Safety Research Center, Fire Insurers Laboratories of Korea 4Member, Principal Researcher, Risk & Safety Research Center, Fire Insurers Laboratories of Korea 5Principal Researcher, Risk & Safety Research Center, Fire Insurers Laboratories of Korea |
Corresponding author:
Heewon Seo, Tel: +82-31-887-6684, Fax: +82-31-887-6720, Email: hwseo@kfpa.or.kr |
|
|
|
|
| Abstract |
|
Experiments were conducted for 27 cases to investigate the spread of fire caused by the radiant heat of fire shutters and its impact on adjacent commodities during a fire. These cases combined two types of shutters (steel and screen fire shutters), four separation distances (1, 2, 3, and 4 m), and four types of storage items (paper, wood, plastic, and wrapped paper boxes). To further evaluate the effects of wrapping, supplementary experiments were performed for four cases involving wooden and plastic boxes. The experimental results demonstrated that paper boxes ignited the most readily, followed by wood and plastic boxes. Upon ignition, the radiant heat flux exceeded 10, 12, and 18 kW/m2 for the paper, wood, and plastic boxes, respectively. Based on these findings, we propose a radiant heat-blocking performance criterion of 10 kW/m2 or less for opening protective devices such as fire shutters. |
| Key Words:
Fire Shutter, Radiant Heat, Ignition Experiment, Radiant Heat Blocking Performance Criteria |
| 요지 |
|
방화셔터의 화재 시 복사열 영향에 의한 수용물품 착화실험을 통한 화재확산을 확인하기 위해서 셔터 2종(철재 방화셔터, 스크린 방화셔터), 이격거리 4개소(1 m, 2 m, 3 m, 4 m), 수용물품 4종(종이⋅목재⋅플라스틱⋅랩핑이 된 종이 상자)의 조합으로 총 27개 Case에 대한 실험을 진행하였다. 그리고, 랩핑의 영향에 대한 추가적인 확인을 위하여 목재상자 및 플라스틱상자에 대한 4개 Case에 대한 추가 실험을 진행하였다. 실험 결과, 종이상자, 목재상자, 플라스틱상자 순으로 착화가 빨리 이루어지는 것을 확인할 수 있었으며, 착화 시 복사열량은 종이상자, 목재상자, 플라스틱상자의 경우 각각 10 kW/m2, 12 kW/m2, 18 kW/m2를 초과한 값을 나타내고 있었다. 이에 방화셔터 등 화재확산방지설비의 복사열 차단 성능기준을 10 kW/m2 이하로 제안하고자 한다. |
| 핵심용어:
방화셔터, 복사열, 착화실험, 복사열 차단 성능기준 |
|