J. Korean Soc. Hazard Mitig Search

CLOSE


J. Korean Soc. Hazard Mitig. > Volume 26(5); 2026 > Article
소방방재
Journal of the Korean Society of Hazard Mitigation 2026;26(5):197-207.
DOI: https://doi.org/10.9798/KOSHAM.2026.26.5.197    Published online October 31, 2026.
리튬이온 파우치셀 수 증가에 따른 열폭주의 열적 및 열방출 특성 분석
장건영1, 홍기현2, 박경훈3
1정회원, (재)한국화학융합시험연구원 방재기술팀 책임연구원
2정회원, (재)한국화학융합시험연구원 방재기술팀 선임연구원
3정회원, (재)한국화학융합시험연구원 방재기술팀 팀장
Analysis of Thermal and Heat-Release Characteristics of Thermal Runaway with Increasing Number of Lithium-Ion Pouch Cells
KunYoung Jang1, KiHyun Hong2, KyungHoon Park3
1Member, Head Researcher, Disaster Prevention Technology Team, Korea Testing & Research Institute
2Member, Senior Researcher, Disaster Prevention Technology Team, Korea Testing & Research Institute (KTR)
3Member, Team Leader, Disaster Prevention Technology Team, Korea Testing & Research Institute (KTR)
Corresponding author:  KunYoung Jang, Tel: +82-41-635-0493, Fax: +82-41-635-0495, 
Email: jangky@ktr.or.kr
Received: 18 September 2026   • Revised: 21 September 2026   • Accepted: 1 October 2026
Abstract
With the increasing use of lithium-ion batteries (LIBs), the need for an effective response to thermal runaway fires has become increasingly important. To evaluate the performance of fire extinguishers specifically designed for battery fires, the scale and thermal behavior of thermal runaway fire sources must be quantified. In this study, the thermal runaway characteristics of lithium-ion pouch cells were investigated as a function of cell number. Test specimens consisting of 1-10 pouch cells were prepared, and thermal runaway was induced using a heating film. The intercell temperature, heat release rate, and total heat release (THR) were measured. The peak heat-release rate generally increased with the number of cells, although variations were observed among the test conditions, and the coefficient of determination from the linear regression analysis was 0.7494. The THR tended to increase relatively consistently with the number of cells, with a coefficient of determination of 0.9573. However, because each cell number condition was tested only once, the regression results should be interpreted as representing the specific experimental conditions rather than as generalized statistical relationships. The study results can serve as fundamental data for examining fire sources and performance evaluation conditions for battery-specific fire extinguishers and extinguishing agents requiring further verification through repeated testing.
Key Words: Lithium-Ion Pouch Cell, Thermal Runaway, Heat Release Rate (HRR), Total Heat Release (THR)
요지
최근 리튬이온 배터리 사용 증가에 따라 열폭주 화재에 대한 대응 필요성이 높아지고 있다. 배터리 전용 소화기의 성능을 평가하기 위해서는 열폭주 화원의 규모와 열적 거동을 정량적으로 설정할 필요가 있다. 이에 본 연구에서는 리튬이온 파우치셀 수 증가에 따른 열폭주 열적 특성을 분석하였다. 파우치셀을 1개부터 10개까지 구성하고 Heating Film으로 열폭주를 유도하여 셀 간 온도, 열방출률(HRR) 및 총방출열량(THR)을 측정하였다. 분석 결과, 최대 열방출률(PHRR)은 셀 수 증가에 따라 전반적으로 증가하였으나 조건별 변동이 나타났으며, 선형회귀분석의 결정계수는 0.7494로 나타났다. 총방출열량(THR)은 셀 수 증가에 따라 상대적으로 일관된 증가 경향을 나타냈으며, 결정계수는 0.9573으로 나타났다. 다만 각 셀 수 조건을 1회 시험하였으므로 본 회귀분석 결과는 해당 실험조건에서 관찰된 변화 경향을 나타내는 제한적인 결과로 해석하였다. 본 연구 결과는 향후 반복시험을 통한 재현성 검증을 전제로 배터리 전용 소화기 및 소화약제의 시험화원 및 성능평가 조건을 검토하기 위한 기초자료로 활용될 수 있을 것으로 판단된다.
핵심용어: 리튬이온 파우치셀, 열폭주, 열방출률(HRR), 총방출열량(THR)


ABOUT
ARTICLE CATEGORY

Browse all articles >