| 대형자동방화셔터 배럴의 처짐 방지를 위한 배럴지지브라켓의 구조안전성 평가 및 설계 방안 |
|
심현보1, 서희원2, 김대회3, 이승재4, 손종원5, 홍성호6 |
1정회원, 한국화재보험협회부설방재시험연구원 방재연구센터 전문위원 2정회원, 한국화재보험협회부설방재시험연구원 수석연구원 3정회원, 한국화재보험협회부설방재시험연구원 방재연구센터 수석연구원 4정회원, 한국화재보험협회부설방재시험연구원 방재연구센터 책임연구원 5정회원, 한국화재보험협회부설방재시험연구원 방재연구센터 선임연구원 6정회원, 한국화재보험협회부설방재시험연구원 방재연구센터 수석연구원 |
| Structural Safety Evaluation and Design Method for Barrel-Support Brackets to Prevent Barrel Deflection in Large Automatic Fire Shutters |
|
Hyeonbo Shim1, Heewon Seo2, Daehoi Kim3, Seungjea Lee4, Jong Won Shon5, Sungho Hong6 |
1Member, Research Fellow, Risk & Safety Research Center, Fire Insurers Laboratories of Korea 2Member, Principal Researcher, Risk & Safety Research Center, Fire Insurers Laboratories of Korea 3Member, Principal Researcher, Risk & Safety Research Center, Fire Insurers Laboratories of Korea 4Member, Senior Researcher, Risk & Safety Research Center, Fire Insurers Laboratories of Korea 5Member, Research Researcher, Risk & Safety Research Center, Fire Insurers Laboratories of Korea 6Member, Principal Researcher, Risk & Safety Research Center, Fire Insurers Laboratories of Korea |
Corresponding author:
Heewon Seo, Tel: +82-31-887-6684, Fax: +82-31-887-6720, Email: hwseo@kfpa.or.kr |
|
Received: 27 August 2026 • Revised: 28 August 2026 • Accepted: 11 September 2026 |
|
|
| Abstract |
|
Large automatic fire shutters, widely used in expansive open spaces such as logistics facilities, are highly susceptible to barrel deflection and collapse when exposed to fire temperatures exceeding 1,000 ℃. However, the current Korean evaluation criterion, limited to 538 ℃, is insufficient for assessing their structural performance under realistic fire conditions. Therefore, this study evaluated barrel deflection and investigated the design of barrel-support brackets based on BS EN 15269-10 and BS EN 15269-11. The results revealed that, under the conditions established in this study, the barrel deflection exceeded the allowable limit in some configurations that were 6 m or greater in width. Furthermore, the minimum required load-bearing capacity of the barrel-support brackets was determined, confirming that the proposed design can effectively prevent excessive barrel deflection and ensure structural stability. |
| Key Words:
Logistics Facility, Large Automatic Fire Shutter, Barrel Deflection, Barrel Support Bracket |
| 요지 |
|
물류시설과 같이 대공간 환경에서 주로 사용되는 대형자동방화셔터의 경우 화재 시 1,000 ℃ 이상의 고온 노출로 인하여 배럴 처짐 및 탈락 위험이 크나, 현행 국내 기준(538 ℃)으로는 이를 평가하기에는 한계가 있다. 이에 본 연구는 영국 BS EN 15269-10, -11을 바탕으로 배럴의 처짐량을 산정하고, 배럴지지브라켓 설계안을 검토하였다. 본 연구에서 설정한 조건에서는 너비 6 m 이상의 일부 규격에서 배럴이 한계처짐량을 초과하는 것이 확인되었으며, 이에 따라 배럴지지브라켓의 최소 지지력을 산정하여 배럴의 처짐 방지 및 구조적 안전성을 확보할 수 있음을 확인하였다. |
| 핵심용어:
물류시설, 대형자동방화셔터, 배럴의 처짐, 배럴지지브라켓 |
|