| CONTAM을 이용한 고층 건축물 부속실 제연설비의 차압 및 방연풍속 특성 분석 |
|
장유리1, 고은성2, 김동민3 |
1정회원, 한빛안전기술단 기업부설연구소 선임연구원 2정회원, 한빛안전기술단 기업부설연구소 연구실장 3정회원, 한빛안전기술단 기업부설연구소 연구소장 |
| Analysis of Pressure Differential and Smoke-Blocking Air Velocity of Vestibule Smoke Control Systems in a High-Rise Building Using CONTAM |
|
Yuri Jang1, Eunseong Go2, Dongmi Kim3 |
1Member, Senior Researcher, R&D Center, Hanbit Safety Technology Group Corporate 2Member, Director, R&D Center, Hanbit Safety Technology Group Corporate 3Member, CTO, R&D Center, Hanbit Safety Technology Group Corporate |
Corresponding author:
Dongmi Kim, Tel: +82-70-4895-1191, Fax: +82-2-6008-8179, Email: kdm5516@naver.com |
|
Received: 4 September 2026 • Revised: 7 September 2026 • Accepted: 28 September 2026 |
|
|
| Abstract |
|
Pressurized smoke control systems in high-rise buildings are affected by vertical shafts, leakage characteristics, and stack effects. In this study, CONTAM was used to examine the pressure differential and smoke-blocking air velocity of a vestibular smoke control system under normal and winter conditions. Under normal conditions, relatively high pressure differentials were observed in several basement smoke control zones. The modification of the exhaust air path reduced these values to approximately 46-60 Pa. On the upper floors, smoke-blocking air velocities ranged from 0.83 to 0.93 m/s. During winter, the neutral pressure level was estimated to be near the 12th floor, with pressure differentials increasing at higher elevations. Under the building and analysis conditions considered in this study, smoke control performance was found to vary considerably with building height and pressure distribution, indicating the need to evaluate the system over the full height of the building. |
| Key Words:
CONTAM, Smoke Control, Stack Effect, Pressure Differential, Smoke-Blocking Air Velocity |
| 요지 |
|
고층건축물의 급기가압 제연설비는 수직샤프트, 개구부 누설특성 및 연돌효과 등에 따라 층별 압력분포가 달라질 수 있다. 본 연구에서는 CONTAM을 이용하여 고층건축물 부속실의 평상시 및 동절기 조건에 따른 차압과 방연풍속을 분석하였다. 평상시 조건에서 지하층 일부 제연구역에 높은 차압이 발생하였으나, 유입공기 배출경로를 조정한 결과 약 46~60 Pa로 감소하였으며, 고층부 방연풍속은 0.83~0.93 m/s로 나타났다. 동절기 조건에서는 약 12층 부근이 중성대 추정 위치로 나타났으며, 상층부로 갈수록 차압이 증가하였다. 따라서 본 연구의 대상 및 해석조건에서는 개별 제연구역뿐만 아니라 건축물 전체의 압력분포를 함께 고려할 필요가 있는 것으로 판단된다. |
| 핵심용어:
CONTAM, 제연설비, 연돌효과, 차압, 방연풍속 |
|