| 국내 데이터 센터 입지 측면의 침수 위험 및 제도개선 방향 |
|
김경준1, 양우현2, 김지유3, 김도현4, 정재학5 |
1정회원, 국립재난안전연구원 잠재재난위험분석센터 시설연구관 2정회원, 국립재난안전연구원 잠재재난위험분석센터 안전연구사 3정회원, 국립재난안전연구원 잠재재난위험분석센터 책임연구원 4국립재난안전연구원 잠재재난위험분석센터 청년인턴 5정회원, 국립재난안전연구원 잠재재난위험분석센터 센터장 |
| Inundation Risks and Institutional Improvement Measures for Data Center Siting in Korea |
|
Kyoungjun Kim1, Woohyun Yang2, Jiyu Kim3, Dohyun Kim4, Jaehak Chung5 |
1Member, Senior Research Officer, Center for Disaster Risk Identification and Assessment, National Disaster Management Research Institute 2Member, Research Officer, Center for Disaster Risk Identification and Assessment, National Disaster Management Research Institute 3Member, Principal Researcher, Center for Disaster Risk Identification and Assessment, National Disaster Management Research Institute 4Intern, Center for Disaster Risk Identification and Assessment, National Disaster Management Research Institute 5Member, Division Director, Center for Disaster Risk Identification and Assessment, National Disaster Management Research Institute |
Corresponding author:
Kyoungjun Kim, Tel: +82-52-928-8610, Fax: +82-52-928-8149, Email: kjkim96@korea.kr |
|
Received: 31 August 2026 • Revised: 2 September 2026 • Accepted: 30 September 2026 |
|
|
| Abstract |
|
We frequently experience serious worldwide damages associated with the disruptions in digital service systems—so-called digital blackouts—owing to the rising inundation risks posed mainly by climate change. This study analyzed the inundation risks of the data centers located in Korea and proposed countermeasures to address them. We used the locations of data centers in Korea and the Flood Risk Maps by the Ministry of Environment (Ministry of Climate, Energy and Environment). For a 500-year return period flood, it was found that 52% of the data centers could be affected by the inundation risks, and 30% of the centers were located in the areas vulnerable to inland inundation. Moreover, the preparedness of the legislative system was limited with insufficient measures. Therefore, the relevant regulations and measures need to be revised, with a review of the TIA-942 guidelines and the characteristics of data center locations, including vulnerability to inland inundations. |
| Key Words:
Data Center, Inundation Risks, Digital Blackout |
| 요지 |
|
기후변화로 인해 침수 위험이 증가하고, 동시에 전세계적으로 시스템의 중단, 즉 디지털 블랙아웃으로 인한 막대한 피해를 경험하고 있는 상황이다. 본 연구에서는 위치선정 관점에서 우리나라 데이터 센터의 침수 위험을 검토하고 개선방향을 제시했다. 이를 위해 환경부(현 기후에너지환경부)에서 발표한 홍수위험지도와 우리나라 데이터 센터 위치 정보를 활용하여 침수 위험을 검토하였다. 그 결과 우리나라에 설치된 데이터 센터의 52%가 500년 빈도의 홍수에 대한 침수위험에 노출되어 있으며 도시침수에 의해서는 30%에 이르는 데이터 센터가 영향을 받을 수 있는 것으로 나타났다. 제도적 측면에서도 대규모 침수 발생을 고려하지 못하고 있었으며, 데이터센터에 관한 정보통신 인프라 표준(TIA 942)에서와 같이 데이터 센터 설치 전 침수 위험에 대한 면밀한 검토 등이 제도적으로 보완되어야 할 필요가 있다. 특히 도시침수와 같이 TIA 942에서 고려하지 못하는 상황에 대해서도 우리나라의 특성을 반영한 대비책이 마련되어야 한다. |
| 핵심용어:
데이터 센터, 침수 위험, 디지털 블랙아웃 |
|