물류시설 방화구획 완화 시 적용되는 수막설비의 효용성에 관한 연구 |
서희원1, 손종원2, 김대회3, 홍성호4, 이상범5, 임성빈6 |
1정회원, 한국화재보험협회부설방재시험연구원 방재연구센터 책임연구원 2한국화재보험협회부설방재시험연구원 방재연구센터 전문위원 3정회원, 한국화재보험협회부설방재시험연구원 방재연구센터 수석연구원 4정회원, 한국화재보험협회부설방재시험연구원 방재연구센터 수석연구원 5국립소방연구원 대응기술연구실 연구원 6정회원, 가천대학교 설비⋅소방공학과 박사졸업 |
Levels of Effectiveness of Water Curtain Equipment Applied When Mitigating Fire Compartment Installation of Logistics Facilities |
Heewon Seo1, Jongwon Shon2, Daehoi Kim3, Sungho Hong4, Sangbum Lee5, Seongbin Lim6 |
1Member, Senior Researcher, Risk & Safety Research Center, Fire Insurers Laboratories of Korea 2Research Fellow, Risk & Safety Research Center, Fire Insurers Laboratories of Korea 3Member, Principal Researcher, Risk & Safety Research Center, Fire Insurers Laboratories of Korea 4Member, Principal Researcher, Risk & Safety Research Center, Fire Insurers Laboratories of Korea 5Researcher, Fire Technology Research Division of National Fire Research Institute 6Member, Ph.D., Department of HVAC & Firefighting Engineering, Gachon University |
Corresponding author:
Heewon Seo, Tel: +82-31-887-6684, Fax: +82-31-887-6720, Email: hwseo@kfpa.or.kr |
|
|
Abstract |
Mock-up tests and fire simulations were performed to verify the effectiveness of water curtain equipment in mitigating fire compartment installation of logistics facilities. The radiant-heat-blocking effect of the water curtain equipment differed significantly based on the type of drencher head, and a blocking effect was observed. Additionally, the radiant temperature and heat flux were significantly reduced when the installation intervals of the drencher heads of the water curtain equipment were reduced. Therefore, improving the standards related to the water curtain equipment of logistics facilities, e.g., providing drencher head specifications, restricting the sizes of the openings, and narrowing the installation intervals of the drencher heads, is necessary to ensure the fire safety of water curtain equipment. |
Key Words:
Logistics Facilities, Fire Compartment, Water Curtain Equipments, Effectiveness |
요지 |
물류시설의 방화구획 완화 시 적용되는 수막설비의 효용성을 검증하기 위해서 실물모형 실험 및 화재시뮬레이션을 수행하였다. 실험 및 시뮬레이션 결과, 수막설비의 복사열 차단효과는 드렌처헤드의 종류에 따라 큰 차이를 보였으며, 일정 부분 차단효과가 있는 것으로 나타났다. 또한, 수막설비의 드렌처헤드 설치 간격을 좁게 할 경우 복사열량 및 복사온도가 현격히 낮아지는 것을 확인할 수 있었다. 따라서, 수막설비의 화재안전성 확보를 위해서는 드렌처헤드 사양을 규정하고, 개구부의 크기 제한 및 드렌처헤드의 설치 간격을 좁게 설정하도록 하는 등 물류시설 수막설비 관련 기준을 개선한 필요성이 있다. |