지상변압기 중성선 접지 탈락에 의한 화재위험성 고찰
유재익, 정재희
A Study of Fire Risk Caused by the Disconnection of the Neutral Ground in the PAD-Mounted Transformer
Jae-Ick Yoo, Jae-Hee Joung
Abstract
Some of the PAD-mounted transformers managed by KEPCO share the common neutral ground for both low and high voltages. When the common neutral ground of PAD-mounted transformer is disconnected, high voltage current is supplied to the low voltage circuits due to the current imbalance in the transformers, exposing the residential areas to unexpected high voltage currents supply. As a result, there is increased risk of fire due to damages in low voltage distribution boards and electrical equipments. This work presents recommendations in the design and the maintenance of the PAD-mounted transformers and additional safety measures for low voltage parts to mitigate the risks of fire.
Key Words: PAD-Mounted transformer; Neutral point ground; Electricity fire; Distributor
요지
한국전력공사 지상변압기 중 일부 제조사의 변압기는 고압측 중성점 접지와 저압측 중성점 접지가 공통으로 구성되어 있다. 이러한 변압기로부터 저압수전을 받고 있는 밀집된 주택 및 소형상가는 지상변압기의 중성점 접지가 탈락 시 변압기의 전류불평형률에 따라 저압측에 수천V까지 유입될 수 있다. 따라서 저압수용가의 분전반 및 전기사용 설비 등이 절연파괴로 소손되면서 화재로 이어질 수 있어 화재예방을 위한 지상변압기의 설계 및 관리적 대책과 저압측 수용가의 안전대책을 제시하였다.
핵심용어: 지상변압기; 중성점 접지; 전기화재; 분전반


ABOUT
ARTICLE CATEGORY

Browse all articles >

BROWSE ARTICLES
AUTHOR INFORMATION
Editorial Office
1010 New Bldg., The Korea Science Technology Center, 22 Teheran-ro 7-gil(635-4 Yeoksam-dong), Gangnam-gu, Seoul 06130, Korea
Tel: +82-2-567-6311    Fax: +82-2-567-6313    E-mail: master@kosham.or.kr                

Copyright © 2024 by The Korean Society of Hazard Mitigation.

Developed in M2PI

Close layer
prev next